Opti-ups DS120KC33 Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Stromversorger Opti-ups DS120KC33 herunter. OPTI-UPS DS120KC33 User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken

Inhaltsverzeichnis

Seite 3 - 1 Preface

Drawings 2-2G and 2-2H are assembly diagrams of DS-C33 series 10K&15K Fig. 2-2G

Seite 5 - Fig. 2-2A

2-3 Introduction on function of main module 2-3-1 Rectifier / battery charger (1) Rectifier / battery charger module is using SCR components for tra

Seite 6 - Fig. 2-2B

2-3-2 Introduction to inverter module (1) Uses IGBT as power component. (2) Uses high technology DSP to control the inverter module. (3) Utilize digit

Seite 7 - Fig. 2-2C

EPO 2-3-4 Input start up/protect trigger (1) Start up function. This function is used for delaying the input power during start up or utility recovery

Seite 8 - Fig. 2-2D

2-4 System operation mode 2-4-1 System is normal (Fig. 2-4-1) LoadBatteryPack+-UtilityS3InputprotectionInputswitchManual bypass switchS6S.T.S.Recti

Seite 9

2-4-3 System is powered by battery (fig.2-4-3) LoadBatteryPack+-UtilityS3InputprotectionInputswitchManual bypass switchS6S.T.S.RectifierS4Batteryswitc

Seite 10

2-4-5 EPO switch (fig. 2-4-5) LoadBatteryPack+-UtilityS3InputprotectionInputswitchManual bypass switchS6S.T.S.RectifierS4BatteryswitchInverterTransfor

Seite 11

3 Panel function 3-1 Status indication on LED panel (Fig. 3-1 and Fig 3-2) Fig. 3-1 Fig. 3-2 → Key ←Key ON Key ↑ Key ↓ Key

Seite 12

Table of contents 1.0 Preface ---------------------------------------------------------------------------------------- 1-1 1-1 Introduction ---------

Seite 13

Status indication on LCD/LED panel is divided into 4 modes: (1) System Normal mode: In this mode, only INPUT, RECTIFIER, CHARGE, INVERTER, OUTPUT LEDs

Seite 14

3-3 LCD Panel description MAIN MENUA Date displayB Event storiesC System setD Time displayE Time setSYSTEM SET (1)Basic set (2)User s

Seite 15

(A-1)I/P V RS 000.0V RN 000.0VST 000.0V SN 000.0VTR 000.0V TN 000.0VI/P Freq . : 00.0 HZ I/P I I/P Cap.RN 000.0A 000.00KVASN

Seite 16 - 2-4 System operation mode

SYSTEM SETBasic setUser set(C-1)Please EnterSecurity Code****USER SET1 Alter security NO.2 Battery test3 Communication set4 F. V. C/C set5 Other

Seite 17

USER SET1 Alter security NO.2 Battery test3 Communication set4 F. V. C/C set5 Other setALTER SECURITY NO.Key in old code****Key in new code****BA

Seite 18

BATTERY TEST▓ 30 Seconds□ 1 Month□ 3 Month□ Test OFFSUCCEEDWaitingSUCCEEDSUCCEEDSUCCEED(C-4-2)

Seite 19 - 3 Panel function

F. V. C/C SET1 Frequency set2 System input V3 System output V4 Output voltage5 Charge current6 Charger mode FREQUENCY SET 口50HZ 口60HZSucceedSYST

Seite 20 - 3-2 Function key

OTHER SET1 Buzzer2 Backup time3 Language4 Model type(C-4-5)BUZZER SET口 Silence口 AlarmSucceedLANGUAGE SET 口 English 口 ChineseSucceedM

Seite 21 - Date display

TIME SET DATE 200*/**/ ** TIME **: **:**(F-1)Date/Time SetY / M / D200*/**/**H M S : :Succeed

Seite 22 - O/P I O/P Cap

4 Placement and installation 4-1 Placement 4-1-1 Transporting The UPS system is composed of the main equipment and battery pack. Therefore be carefu

Seite 23 - USER SET

1 Preface 1-1 Introduction DS-C33 series UPS is one of the industry’s most reliable and stable power protection equipment. It is fully controlled by

Seite 24 - OTHER SET

will be installed. 4-2 Installation 4-2-1 Input / Output Specifications System output 50Hz/60Hz 3 wire 3 phase wire 200Vac, 220Vac 50Hz/60Hz 3 phase

Seite 25

Table 4-2-1 When installing the UPS, please refer to table of 4-2-1 for corresponding input/output circuit breaker. Refer to table 4-2-2 for wire spec

Seite 26

Table 4-2-2A For wire diameters for different capacity of UPS system, please check the table 4-2-2B below Wire diameter of ground wire 10KVA 8mm2 1

Seite 27 - MODEL SET

4-2-3 Input/Output connection and precaution From table 4-2-1 and table 4-2-2, we could determine the installation wire diameter and breaker capacity,

Seite 28 - TIME SET

After wiring, please check the following points listed below. (1) Screws in each point are tight. (2) Ground wire is connected well. (3) No short-circ

Seite 29 - 4-1 Placement

Table for battery cable diameter corresponding to capacity of UPS UPS capacity Battery cable diameter (mm2) 10KVA 5.5mm2 15KVA 8mm2 22.5KVA 14mm2 3

Seite 30 - 4-2 Installation

5 Operation procedure 5-1 Start up procedure 5-1-1 Initial start up procedure (1) Introduction to switches inside the equipment and its function S1

Seite 31

(5) 1.Initial start up procedure: Make sure all the loads connected to the UPS are switched off. Turn on Switch S1, S2 and turn off S3 in sequence. T

Seite 32

Fig. 5-1-1

Seite 33

5-1-2 General start up procedure After the system is initialized successfully and shut down, please follow the steps below to start up the equipment a

Seite 34

2 System structure 2-1 System Diagram of DS-C33 (12) (5) (7) LoadBatteryPack+-S3S6S4S5S1

Seite 35

Fig. 5-3

Seite 36 - 5 Operation procedure

5-3-2 Procedure for replacing battery (1) Turning off the INVERTER Push “OFF” button on the front panel and then push “ENTER” button to shut down UPS.

Seite 37

5-4 System recovery from maintenance procedure Turn ON switch S1 (for some UPS models only), S2 (for some UPS models only), S3 and S5, Turn off S6

Seite 38

5-5 Introduction to LCD front panel and illustration of each function Introduction to function keys on the front panel → button: Moves the page curs

Seite 39 - 5-3 Maintenance procedure

6 Maintenance (1) Keep the operating environment clean and clean the inside of the UPS at least once a year. (2) Discharge and charge the battery at

Seite 40 - Fig. 5-3

7 Specifications for DS-C33 Series UPS Model DS 10KC33 DS 15KC33 DS 22.5KC33DS 30KC33DS 45KC33DS 60KC33 DS 80KC33 DS 100KC33DS 120KC33Capacity 10KVA

Seite 41

Model DS 10KC33 DS 15KC33 DS 22.5KC33DS 30KC33DS 45KC33DS 60KC33 DS 80KC33 DS 100KC33DS 120KC33W 530mm 530mm 530mm 530mm 750mm 750mm 750mm 1100mm 110

Seite 42

8 DS-C33 Series troubleshooting 8-1 Simple troubleshooting chart Error message displayed Error description Troubleshooting Input over-voltage (1

Seite 43

Voltage of DC chain voltage is too high (1)Ol-3302DCvoltage feedbacks point open circuit Recover feedbacks circuit (2)Ol-3302 feedbacks circuit erro

Seite 44 - 6 Maintenance

8-2 Simple troubleshooting for Inverter Error message displayed Error description Troubleshooting Output over-voltage (1)Ol-3320 detects circuit er

Seite 45

2-2 System assembly and parts layout Drawings 2-2A and 2-2B are the assembly diagrams of DS-C33 series 100K, 120K Fig. 2-2A FanINV/Driver Board

Seite 46

8-3 Simple troubleshooting for system function Error message displayed Description Troubleshooting (1)No battery found Add battery (2)Battery powe

Seite 47

(1)Input power to low or no utility Recover utility to within+/-20%(2)Battery voltage decreases to low voltage point Unload to 10%~20% of load (3)Ol-

Seite 48

Fig. 2-2B Rectifier/Charger Module12 Pluse Power Sensor BoardRectifier/Charger Control BoardFanDC CapacitanceINV TransformerDC ChokeInput Rela

Seite 49

Drawings 2-2C and 2-2D are the assembly diagrams of DS-C33 series 45K, 60K, 80K Fig. 2-2C

Seite 50

Fig. 2-2D

Seite 51

Drawings 2-2E and 2-2F are the assembly diagrams of DS-C33 series 22.5K, 30K. Fig. 2-2E