Opti-ups PS500C Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Werkzeug Opti-ups PS500C herunter. OPTI-UPS PS500C User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 1
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
500VA/300W 700VA/420W
25.
PS500C / PS700C
Features
SpecificationsFront Panel
* Pure Sine wave
* Line-interactive design
* Boost and buck AVR
* Overload, AVR, on-line, back up and battery status LEDs display
* Fully digitized microprocessor control
* RS-232 or USB communication port (500VA~700VA models)
* RS-232 and USB communication port (1000VA~3000VA models)
* PS500C / PS700C
Rear Panel
PS500C / 700C
windows
2000 / XP
2003 / Vista
PS500C
PS700C
UPS automatic shutdown if overload exceeds 110%
of nominal for 20 seconds and 125% for 2 seconds
12.6 x 3.8 x 5.3 / 16 x 7.6 x 10.2
320 x 97 x 135 / 406 x 192 x 258
Battery test, UPS ON/OFF Schedule,
AC input/output power status display
Elevation: 3,500m max, Humidity: 0%-95%(without
condensation formation), Temperature: 0-40 deg C
<40dBA (1 meter from surface)
15000 meters max. elevation
14.5 / 16.3 15.6 / 17.4
6.6 / 7.4 6.7 / 7.9
Typology
On-battery Output Wave Form
Line-Interactive
Pure Sine Wave
(in)
(mm)
(lbs)
(kg)
Capacity
Voltage
Frequency
Voltage (on battery)
Frequency (on battery)
Voltage Regulation AVR
Spike Protection
Unit Input
EMI/RFI filter
Overload protection
Transfer Time
Short Circuit
Type
Typical Recharge Time
User Replaceable Battery
Protection
Back-up Time
Battery Back-Up
Battery Low
Overload
RS-232 or USB Interface
Operation
Audible noise
Storage condition
Net Weight Kg(Net/Gross)
Dimension (Physical/ Packing)
(L x W x H)
100V, 110V, 115V, 120V / 220V, 230V, 240V*
50 or 60Hz +/-10% (auto sensing)
Pure sine wave output at nominal +/-5%
50 or 60Hz +/-0.5%
INPUT
OUTPUT
PROTECTION AND FILTERING
BATTERY
ALARM
INTERFACE
ENVIRONMENT
PHYSICAL
AVR automatically increases output voltage 15% above input voltage when input voltage
drops lower than 9% from nominal. AVR decreases output voltage 13% below input voltage
when input voltage rises higher than 9% from nominal.
* Lightning and surge protection
* Short circuit and overload protection
* 50/60Hz frequency auto sensing
* Tel / modem / internet spike protection
* Cold start (DC power on)
* Hot swappable battery
* SNMP card slot (PS1000C-PS3000C)
PS500C / PS700C
Line Normal
Backup
Boost AVR
Buck AVR
Fault
On / Test
Off
INREMOTE
PORT
INPUT
SURGE PROTECTED OUTLET
BATTERY BACKUP OUTLETS
OUT
INREMOTE
PORT
OUT
INPUT
CURCUIT
BREAKER
CONVENIENCE OUTLET
BATTERY BACKUP OUTLETS
USB
RJ11 / RJ45
Circuit Breaker
Suge Protected Outlets
Input
INREMOTE
PORT
INPUT
SURGE PROTECTED OUTLET
BATTERY BACKUP OUTLETS
OUT
USB
RJ11 / RJ45
Surge Protected
Outlets
Battery Backup Outlets
Fuse
110V / 120V
220V / 230V / 240V
Sine Wave
320 Joules, 2ms
Fuse or Circuit breaker for overload & short circuit protection
10dB at 0.15MHz, 50dB at 30MHz
2~4 milliseconds (typical)
UPS output cut off immediately or input open protection
Sealed, maintenance free lead-acid
4 hours (to 90% of full capacity)
Automatic self-test & deep discharge protection,
Replace battery indicator
10 - 30 minutes (depending on computer load)
Slow beeping sound (about 0.25Hz)
Rapid beeping sound (about 1.00Hz)
Continuous beeping sound
Battery Backup Outlets
Input
12V / 7AH x 1
12V / 34W x 1
Line Interactive
UPS Series
On Line UPS
Series
AVR Series
Networking
Series
Inverter Series
Surge Series
Green Power
Series
Standby UPS
Series
* See VS1000C on page 6
Seitenansicht 0
1

Inhaltsverzeichnis

Seite 1 - * PS500C / PS700C

500VA/300W 700VA/420W25.PS500C / PS700CFeaturesSpecificationsFront Panel* Pure Sine wave * Line-interactive

Kommentare zu diesen Handbüchern